POWER AND DERATING

The rated power is the maximum available during the PRP Prime Power ISO according to Standard 8528.1 and it is guaranteed within 5% after the engine has been run in.

This value is reduce of the:
  • by 1% every 100 meters in altitude


  • by 2% every 5°C above 20°C


  • and by 10% for COP Continuous Power in compliance with ISO Standard 8528.1.